Installation Procedure
English
Installation Procedure
CAUTION
Dependingontheconditionofpowersupply,
unstablepowerorvoltagemaycausemalfunction
ofthepartsorcontrolsystem.(Attheshiporplaces
usingpowersupplyfromelectricgenerator...etc)
Installtheunitinaplacewherewatercandrain
smoothly.
Ifyouhaveanydifficultyfindinginstallationlocationas
prescribedabove,contactyourmanufacturerfordetails.
Besuretocleantheseawaterandthedustonthe
heatexchangeroftheoutdoorunitandapplya
corrosioninhibitoronit.(Atleastonceinayear.)
Checktheconditionoftheproductperiodically.
Checktheinstallationsiteevery3monthsand
performanti-corrosiontreatmentsuchasR-Pro
suppliedbySAMSUNG(Code:MOK-220SA)or
commercialwaterrepellentgreaseandwax,
etc.,basedontheproductcondition.
Whentheproductistobeshutdownforalong
periodoftime,suchasoff-peakhours,take
appropriatemeasureslikecoveringtheproduct.
Iftheproductinstalledwithin500mofseashore,
specialanti-corrosiontreatmentisrequired.
※PleasecontactyourlocalSAMSUNGrepresentative
forfurtherdetails.
Outdoor unit dimensions
(Unit: mm)
A Type
AC012TXQLEC
285
790
50
551.7
12
60
548
336
Minimum clearances for the outdoor unit
When installing 1 outdoor unit
(Unit: mm)
300 or more
1500 or more
300 or
more
600 or
more
300 or
more
2000
or more
1500
or more
600
or more
300
or more
1500
or more
300 or
more