Handleiding
Je bekijkt pagina 26 van 31

26
English
Appendix
Troubleshooting
Thetablebelowlisttheself-diagnosticroutines.Forsomeoferrorcodes,youmustcontactanauthorized
servicecentre.
Ifanerroroccursduringtheoperation,itisdisplayedontheoutdoorunitPCBLED,bothMAINPCBand
INVERTERPCB.
1 E108
Errorduetoduplicatedcommunicationaddress Checkonrepeatedindoorunitmainaddress
2 E121
Erroronroomtemperaturesensorofindoorunit(Short
orOpen)
IndoorunitRoomThermistorOpen/Short
3 E122
ErroronEVAINsensorofindoorunit(ShortorOpen) IndoorunitEVA_INThermistorOpen/Short
4 E123
ErroronEVAOUTsensorofindoorunit(ShortorOpen) IndoorunitEVA_OUTThermistorOpen/Short
5 E153
Erroronfloatswitch(2nddetection)
IndoorunitFloatSwitchOpen/ShortDrainPump
operationCheck
6 E154
Indoorfanerror CheckonindoorunitindoorFanoperation
7 E198
Erroronthermalfuseofindoorunit(Open) ThermalFuseOpenCheckofindoorunitTerminalBlock
8 E201
Communicationerrorbetweentheindoorunitand
outdoorunit(Pre-trackingfailureorwhentheactual
numberofindoorunitsaredifferentfromtheindoorunit
quantitysettingontheoutdoorunit)
Errorduetocommunicationtrackingfailureafterinitial
powerissupplied(Theerroroccursregardlessofthe
numberofunits.)
Checkindoorquantitysettinginoutdoor
9 E202
Communicationerrorbetweenindoorunitandoutdoor
unit(Whenthereisnoresponsefromindoorunitsafter
trackingiscompleted)
Checkelectricalconnectionandsettingbetweenindoor
unitandoutdoorunit
10 E203
Communicationerrorbetweentheoutdoorunitand
mainmicom(ForPF#4to#6controllers,errorwillbe
determinedfromthetimewhenthecompressoristurned
on.)
Checkelectricalconnectionandsettingbetweenoutdoor
unitMAINPBA-INVERTERPBA
11 E221
Erroronoutdoortemperaturesensor(ShortorOpen) CheckOutdoorsensorOpen/Short
12 E231
ErroronoutdoorCONDOUTsensor(ShortorOpen) CheckCond-OutsensorOpen/Short
13 E251
Errorondischargetemperaturesensorofcompressor1
(ShortorOpen)
CheckDischargesensorOpen/Short
14 E320
ErroronOLPsensor(ShortorOpen) CheckOLPsensorOpen/Short
15 E403
Compressordownduetofreezeprotectioncontrol CheckOutdoorCond.
16 E404
Systemstopduetooverloadprotectioncontrol CheckComp.whenitstarts
17 E416
Systemstopduetodischargetemperature -
18 E422
Blockagedetectedonhighpressurepipe
1.Checkiftheservicevalveisopen
2.Checkforrefrigerantleakage(pipeconnections,heat
exchanger)andchargerefrigerantifnecessary
3.Checkifthere'sanyblockageontherefrigerantcycle
(indoorunit/outdoorunit)
4.Checkifadditionalrefrigeranthasbeenaddedafter
pipeextension
19 E425
Reversephaseoropenphase Checkwhether3phaseisreversedoropened.