Samsung AC012TXQLEC handleiding

31 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 26 van 31
26
English
Appendix
Troubleshooting
Thetablebelowlisttheself-diagnosticroutines.Forsomeoferrorcodes,youmustcontactanauthorized
servicecentre.
Ifanerroroccursduringtheoperation,itisdisplayedontheoutdoorunitPCBLED,bothMAINPCBand
INVERTERPCB.
1 E108
Errorduetoduplicatedcommunicationaddress Checkonrepeatedindoorunitmainaddress
2 E121
Erroronroomtemperaturesensorofindoorunit(Short
orOpen)
IndoorunitRoomThermistorOpen/Short
3 E122
ErroronEVAINsensorofindoorunit(ShortorOpen) IndoorunitEVA_INThermistorOpen/Short
4 E123
ErroronEVAOUTsensorofindoorunit(ShortorOpen) IndoorunitEVA_OUTThermistorOpen/Short
5 E153
Erroronfloatswitch(2nddetection)
IndoorunitFloatSwitchOpen/ShortDrainPump
operationCheck
6 E154
Indoorfanerror CheckonindoorunitindoorFanoperation
7 E198
Erroronthermalfuseofindoorunit(Open) ThermalFuseOpenCheckofindoorunitTerminalBlock
8 E201
Communicationerrorbetweentheindoorunitand
outdoorunit(Pre-trackingfailureorwhentheactual
numberofindoorunitsaredifferentfromtheindoorunit
quantitysettingontheoutdoorunit)
Errorduetocommunicationtrackingfailureafterinitial
powerissupplied(Theerroroccursregardlessofthe
numberofunits.)
Checkindoorquantitysettinginoutdoor
9 E202
Communicationerrorbetweenindoorunitandoutdoor
unit(Whenthereisnoresponsefromindoorunitsafter
trackingiscompleted)
Checkelectricalconnectionandsettingbetweenindoor
unitandoutdoorunit
10 E203
Communicationerrorbetweentheoutdoorunitand
mainmicom(ForPF#4to#6controllers,errorwillbe
determinedfromthetimewhenthecompressoristurned
on.)
Checkelectricalconnectionandsettingbetweenoutdoor
unitMAINPBA-INVERTERPBA
11 E221
Erroronoutdoortemperaturesensor(ShortorOpen) CheckOutdoorsensorOpen/Short
12 E231
ErroronoutdoorCONDOUTsensor(ShortorOpen) CheckCond-OutsensorOpen/Short
13 E251
Errorondischargetemperaturesensorofcompressor1
(ShortorOpen)
CheckDischargesensorOpen/Short
14 E320
ErroronOLPsensor(ShortorOpen) CheckOLPsensorOpen/Short
15 E403
Compressordownduetofreezeprotectioncontrol CheckOutdoorCond.
16 E404
Systemstopduetooverloadprotectioncontrol CheckComp.whenitstarts
17 E416
Systemstopduetodischargetemperature -
18 E422
Blockagedetectedonhighpressurepipe
1.Checkiftheservicevalveisopen
2.Checkforrefrigerantleakage(pipeconnections,heat
exchanger)andchargerefrigerantifnecessary
3.Checkifthere'sanyblockageontherefrigerantcycle
(indoorunit/outdoorunit)
4.Checkifadditionalrefrigeranthasbeenaddedafter
pipeextension
19 E425
Reversephaseoropenphase Checkwhether3phaseisreversedoropened.
Appendix
Appendix

Bekijk gratis de handleiding van Samsung AC012TXQLEC, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkSamsung
ModelAC012TXQLEC
CategorieAirco
TaalNederlands
Grootte5260 MB