Appendix
No.
Error
Code
Meaning Remarks
20 E440
Heatingoperationrestrictedatoutdoortemperatureover
Theat_highvalue(default:30°C)
1.Checktherangeoftemperaturelimitedforheating
operation
2.Checktheoutdoortemperaturesensor
21 E441
Coolingoperationrestrictedatoutdoortemperature
belowTcool_lowvalue(default:0°C)
1.Checktherangeoftemperaturelimitedforcooling
operation
2.Checktheoutdoortemperaturesensor
22 E458
Fanspeederror FAN1ERROR
23 E461
Errorduetooperationfailureofinvertercompressor -
24 E462
Systemstopduetofullcurrentcontrol -
25 E463
Overcurrenttrip/PFCovercurrenterror CheckOLPsensor
26 E464
IPMOverCurrent(O.C)
1.Checkiftheservicevalveisopen
2.Checkthestateofrefrigerant
3.CheckifconnectingwireandthepipeareOK
4.Checkthecompressor
27 E465
Comp.Overloaderror -
28 E466
DC-Linkvoltageunder/overerror CheckACPowerandDCLinkVoltage
29 E467
Errorduetoabnormalrotationofthecompressoror
unconnectedwireofcompressor
CheckCompwire
30 E468
Erroroncurrentsensor(ShortorOpen) CheckOutdoorInverterPBA.
31 E469
ErroronDC-Linkvoltagesensor(ShortorOpen) -
32 E470
OutdoorunitEEPROMRead/Writeerror(Option) CheckOutdoorEEPROMData
33 E471
OutdoorunitEEPROMRead/Writeerror(H/W) CheckOutdoorEEPROMPBA
34 E474
ErroronIPMHeatSinksensorofinverter1(Shortor
Open)
CheckOutdoorInverterPBA.
35 E475
Erroroninverterfan2 FAN2ERROR
36 E483
Inverterinputvoltagesensorerror CheckOutdoorInverterPBA
37 E484
PFCOverload(Overcurrent)Error CheckOutdoorInverterPBA.
38 E485
Erroroninputcurrentsensorofinverter1(ShortorOpen) CheckOutdoorEEPROMPBA
39
E488
Inverterinputvoltagesensorerror CheckOutdoorInverterPBA
40 E500
IPMoverheaterroroninverter1 CheckOutdoorInverterPBA.
41 E508
Smartinstallisnotinstalled -
42 E554
Gasleakdetected Checktherefrigerant
43 E556
Errorduetomismatchingcapacityofindoorandoutdoor
unit
Checktheindoorandoutdoorunitcapacity
44 E563
Errorduetomismatchingindoorandoutdoorunit ChecktheoutdoorEEPROMdataandindooroptioncode
45 E557
DPMremotecontrolleroptionerror Checktheindooroptioncode
46 E590
InverterEEPROMChecksumerror -