Proel AE604 handleiding
Handleiding
Je bekijkt pagina 29 van 48

29
• Conf line-out mode Line-Out contents configuration
• Conf master equalization System equalization configuration
• Delete system logs Allows to delete system logs
• System info Displays system information
The DO INDICATOR TEST sub-allows you to test all system indicators.
By pressing OK all indicators will turn on for 2 seconds - even the display will turn completely white - and
the acoustic indicators will emit a continuous beep. If an indicator is off during this operation, or some
pixels do not turn white, or no sound is heard from the system, contact the service centre and report the
fault
The CONF SYSTEM TIME sub-menu allows you to view and configure the system date and time.
To change the system date and time simply press OK to access the Set system time screen. Select the
field to be changed with the RIGHT and LEFT arrows and select the desired value with the UP and DOWN
arrows.
To save the configuration, simply press OK, press BACK to cancel the changes.
The CONF LINE MODE sub-menu allows You to view and configure the speaker lines functioning.
Each line can be activated in single A or A&B mode: DISABLED / Single A / Mode A&B.
In case of ACTIVE A&B line mode, you can configure the volume delta to be applied, in case of a line
fault, to the one still working. In fact, the A&B mode allows you to independently manage the line faults
and, in case of a fault, isolate the faulty line and simultaneously recover the lost sound pressure by
transferring power on the line not in error.
To change the operating parameters simply press OK on the relative speaker line and then select the
desired value with the UP and DOWN arrows.
To save the configuration, simply press OK, press BACK to cancel the changes.
To change the speaker lines configuration you must have access level 3, if not a screen is displayed where
you are required to login to carry out this operation.
NOTE: changing the operating mode of the speaker lines cancels the calibration values of the line
impedance
The CONF ALARM MESSAGE LOOP sub-menu allows you to view and configure the minimum and
maximum number of repetitions of the pre-recorded alarm and evacuation messages.
The minimum number establishes how many times the pre-recorded message is played before accepting
the stop command; the parameter can be disabled by setting the value 0 = DISABLED.
The maximum number establishes how many times at most the pre-recorded message is played before it
is automatically terminated; the parameter can be disabled by setting the value 0 = DISABLED.
The parameters of minimum and maximum number of message playback are only applied to alarm and
evacuation messages.
NOTE: if the configuration of minimum or maximum playback is active for pre-recorded messages during
playback, the main screen will display the symbol.
To change the operating parameters, simply press OK to access the Evac & Alarm msg loop config screen.
Select the desired setting with the RIGHT and LEFT arrows and select the desired value with the UP and
DOWN arrows.
To save the configuration, simply press OK, press BACK to cancel the changes.
To change the minimum and maximum number of alarm and evacuation pre-recorded message
playback, you must have access level 3, if not a screen is displayed where you are required to login to
carry out this operation.
NOTE: The assignment of a maximum or minimum number of repetitions of the alarm message is in
contrast with the requirements of the EN54-16 standard. Therefore only with the parameters left at
the default values or disabled the system meets the requirements of the standard.