SOLARCHECK family
50
PHOENIX CONTACT 105608_en_01
4. Remove the protective foil from the DIP switches.
5. Each module must be assigned a unique Modbus address to allow for error-free com-
munication between the modules. Set a valid Modbus address via the upper DIP
switches using a suitable tool (e.g., micro screwdriver). The default setting is “0” which
means that no communication is possible. Select an address between 1 and 247.
1
23
4
5
6
7
8
ON
ON
1
2
ON
12345678
1
Value
S
-
4
8
-
-
64
77
2=1
0
2=2
1
2=4
2
2=8
3
2=16
4
2=32
5
2=64
6
2 = 128
7
-
Address