Table A-2 Configuration help for selecting Inline terminals for temperature recording
Criterion IB IL TEMP 2
UTH-PAC
IB IL UTH 4/J-
ECO
IB IL UTH 4/K-
ECO
IB IL UTH 4/L-
ECO
2861386 2702502 2702503 2702504
(no longer in
product range)
IB IL TEMP 2
UTH-XC-PAC
2701216
TC
detection
TC detection
(Thermocouple inputs,
e.g., type B, C, E, J, K, N, R, S, T,
U, W, HK)
Yes Yes (type J) Yes (type K) Yes (type L)
Number of TC 2-wire sensors 2 4
Internal cold junction compen-
sation for thermocouple
detection
Yes Yes
Additional connection option for
an external cold junction sensor
(Pt1000, Ni1000)
Yes No
Dynamic
response
Dynamic response of measuring
inputs
High Medium
Measurements/second
(typical for all channels)
30 1.6
Precision Precision Medium Medium
Typical tolerance of Pt100 or TC
(at T
A
= +25°C)
0.6 K + toler-
ance of cold
junction
(TC type K)
±2.5 K ±2.7 K ±2.5 K
(incl. tolerance of cold junction)
Maximum tolerance of Pt100 or
TC (at T
A
= +25°C)
2.4 K + toler-
ance of cold
junction
(TC type K)
±5.1 K ±5.5 K ±5.1 K
(incl. tolerance of cold junction)