When connecting the supply voltages, use the diagnostic and status indicators to check
whether the device has started up correctly or whether any errors are indicated. For
instructions on how to proceed in the event of an error, please refer to “Errors: Messages
and removal” on page 51.
Check mounting and installation. Checklist “Validation” on page 86
Carry out the necessary parameterization.
Assign a device name for the PROFINET IO device function
of the device.
In the software used for parameterization, apply the
PROFIsafe addresses that you set on the safe PROFINET
gateway via DIP switches for the corresponding PROFINET
systems.
Send your settings to the PROFINET IO controller.
Documentation for the software used for parameterization
Documentation for the controller used (PROFIsafe)
“The FL PN/PN SDIO-2TX/2TX safe PROFINET gateway in
software tools” on page 73
“Addressing notes for PROFIsafe devices in PROFINET
systems coupled via a safe PROFINET gateway” on
page 71
Documentation for the PROFINET system
Perform a function test and validation. Check whether the
safety function responds as planned during programming
and parameterization.
Checklist “Validation” on page 86
Table 4-1 Steps for initial startup
Step Relevant section and literature