/SFRT The maximum permissible total response time (safety function response time) for a safety
function is the sum of the maximum signal runtimes (worst case delay times) of all
PROFIsafe devices in PROFINET systems 1 and 2 involved in safety function SF
a
or SF
b
and the data processing time in the safe PROFINET gateway:
Another approach Based on the maximum permissible total response time (safety function response time
SFRT
max
) for the safety function to be implemented, determine the actual total response
time to be implemented (SFRT).
These times are used as the basis for determining the monitoring times to be set for each
individual PROFIsafe device involved in the safety function with an input or output function
(watchdog times: F_WD_Time IN/F_WD_Time OUT).
Once you have determined the upper and lower limits of the monitoring times, allowing for
the safety function to be observed and system availability, specify the actual monitoring
times that are to be set. Set these values in the programming software for each PROFIsafe
device involved in the safety function.
DAT The relevant processing time/cycle time of the PROFIsafe protocol in the safe PROFINET
gateway for calculating the response times, “DAT”, is 5 ms.
The F-Device Acknowledge Time (“DAT”) must be taken into consideration for each side of
the safe PROFINET gateway when determining the monitoring times.
Safety function SF
a
:SFRT
a_max
= ∑ WCDT
1a
+ WCDT
copy
+ ∑ WCDT
2a
Safety function SF
b
:SFRT
b_max
= ∑ WCDT
1b
+ WCDT
copy
+ ∑ WCDT
2b
Please note that safety chains a and b in the machine/system usually include different
safety functions. This typically results in different total response times for both safety
chains, which must be considered separately.
Refer to additional notes for calculating the response times (SFRT) and the monitoring
times (F_WD_Time IN/F_WD_Time OUT) in the system-specific user documentation.