Description of the FL PN/PN SDIO-2TX/2TX
8220_en_06 PHOENIX CONTACT 25
Key:
A Safe PROFINET gateway
WCDT
copy
Worst case delay time of the safe PROFINET gateway
This time is the same for each safety function to be implemented with the
safe PROFINET gateway, regardless of whether safe process data is
being transmitted from system 1 to system 2 or vice versa.
Please refer to “Technical data” on page 61 for this time.
SF
a
Safety function SF
a
(safety chain a)
WCDT
1a
+
WCDT
2a
Sum of the maximum signal runtimes (worst case delay times) of all
PROFIsafe devices in PROFINET systems 1 and 2 that are involved in
safety function SF
a
.
SFRT
a_max
Maximum permissible safety function response time of PROFIsafe
systems 1 and 2 involved in safety function SF
a
and of the safe
PROFINET gateway that is determined for each safety function to be
implemented.
SFRT
a
Safety function response time of PROFIsafe systems 1 and 2 that are in-
volved in safety function SF
a
and of the safe PROFINET gateway that is
actually implemented.
SF
b
Safety function SF
b
(safety chain b)
WCDT
1b
+
WCDT
2b
Sum of the maximum signal runtimes (worst case delay times) of all
PROFIsafe devices in PROFINET systems 1 and 2 that are involved in
safety function SF
b
.
SFRT
b_max
Maximum permissible safety function response time of PROFIsafe
systems 1 and 2 involved in safety function SF
b
and of the safe
PROFINET gateway that is determined for each safety function to be
implemented.
SFRT
b
Safety function response time of PROFIsafe systems 1 and 2 that are in-
volved in safety function SF
b
and of the safe PROFINET gateway that is
actually implemented.