ECM – multifunctional current measuring transducers
38 / 78 Phoenix Contact
111433_en_00
4.1.11 Network settings (only for ...-MTCP devices)
Figure 4-18 Network settings for MTCP devices
Specify the network settings of the device. The following values are preset by default:
Device name
The devices support the NetBios name service. With this protocol, the device can be ad-
dressed using a host name, without knowing the IP address of the device. The device has
two manufacturer-specific and non-modifiable names. The third name can be freely se-
lected. The following names have been defined:
– First manufacturer-specific NetBios name: (e.g., ECM-UC-100A-UI)
– User-specific NetBios name: (default: )
The ECM device acts as a Modbus/TCP server and opens port 502 for commu-
nication. Make sure that port 502 in your network is approved for Modbus/TCP
communication.
Mode Static
IP address 192.168.1.2
Subnet mask 255.255.255.0
Standard gateway 192.168.1.1
DNS server 192.168.1.1
When the dynamic IP assignment is used, the device obtains its IP configura-
tion via the DHCP protocol from another DHCP server in the same network.