ECM – multifunctional current measuring transducers
34 / 78 Phoenix Contact
111433_en_00
4.1.8 Setting the digital output (only for devices with analog output)
Figure 4-12 Settings for relay and transistor output
Idle level
Specify the desired output state for the relay or transistor contact.
Figure 4-13 Settings for relay output Figure 4-14 Settings for transistor output
NOTE: Potential damage to the device!
The transistor output can carry a maximum of 100 mA at 24 V DC. Protect the
transistor output with a fast-blow backup fuse <250 mA.