Configuration
111433_en_00 Phoenix Contact 33 / 78
4.1.7 Setting the analog output (only for devices with analog output)
Figure 4-11 Settings for analog output
Output type
Select one of the standard signal ranges.
The following ranges are available:
Source
Specify which current type should be mapped to the analog output:
– I RMS
– I AC
– I DC
Measurement range start value and end value
Specify the current value in amperes from which the measurement starts and ends. If you
have selected “I RMS” or “I AC” as the source, the lowest value is 0 A. If you have se-
lected “I DC” as the source, you can also specify a negative value as the start value.
Over range detection and under range detection
Select “Over range detection” or “Under range detection” to define an individual current
limit value in ampere at which a freely defined current level is output in milliampere.
Table 4-2 Output type standard ranges
Current ranges Voltage ranges
0 mA ... 20 mA 0 V ... 10 V 2 V ... 10 V -10 V ... 10 V
20 mA ... 0 mA 10 V ... 0 V 10 V ... 2 V 10 V ... -10 V
4 mA ... 20 mA 0 V ... 5 V 1 V ... 5 V -5 V ... 5 V
20 mA ... 4 mA 5 V ... 0 V 5 V ... 1 V 5 V ... -5 V