CHARX PS...87.5KW
46 / 94
PHOENIX CONTACT 109484_en_01
5.5 Requirements on the electrical connection
WARNING: Material damage from incorrect fuses for the mains supply line
Dimension the mains fuse according to the currents specified in the technical data. In-
correct protection can result in operating errors or fire.
When connecting the conductors, please observe the following
• Only insert conductors, but not insulation, into the connection terminal blocks.
• Check that the screw connections of the connection terminal blocks are tight.
• Adapt the screw connections of the cable entries to the cable cross-section.
• Use flexible cables to simplify installation.
Input mains
• Connect the neutral conductor on the input side in any case.
The neutral conductor of the bypass always has to be connected to the neutral conduc-
tor of the mains input.
Marking the phases
Different countries may use their individual phase marking. The following table shows pos-
sible markings.
Supply system configuration
The system can be operated with all IT and TN grids.
Table 5-1 Country-specific phase marking
Three-phase America Europe
L1 R U
L2 S V
L3 T W