CHARX PS...87.5KW
46 / 94
PHOENIX CONTACT 109484_en_01
5.5 Requirements on the electrical connection
WARNING: Material damage from incorrect fuses for the mains supply line
Dimension the mains fuse according to the currents specified in the technical data. In-
correct protection can result in operating errors or fire.
When connecting the conductors, please observe the following
Only insert conductors, but not insulation, into the connection terminal blocks.
Check that the screw connections of the connection terminal blocks are tight.
Adapt the screw connections of the cable entries to the cable cross-section.
Use flexible cables to simplify installation.
Input mains
Connect the neutral conductor on the input side in any case.
The neutral conductor of the bypass always has to be connected to the neutral conduc-
tor of the mains input.
Marking the phases
Different countries may use their individual phase marking. The following table shows pos-
sible markings.
Supply system configuration
The system can be operated with all IT and TN grids.
Table 5-1 Country-specific phase marking
Three-phase America Europe
L1 R U
L2 S V
L3 T W