Phoenix Contact CHARX PS/3AC/920DC/87.5KW handleiding

96 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 36 van 96
CHARX PS...87.5KW
36 / 94
PHOENIX CONTACT 109484_en_01
During mounting, installation, and maintenance, cover the system to protect it against con-
tamination. Every type of contamination, especially conductive contamination, can lead to
an irreparable total failure of the system or the DC power modules.
Access for maintenance and service work
Unfavorable structural conditions or mounting conditions can cause an additional effort.
Ground surface
The ground surface has to be able to bear the weight. Consider some additional weight for
future expansions.
The ground surface has to be level.
The ground surface must not be inflammable.
Indoor climate
The installation location has to be dry and well-ventilated.
The waste air has to be exhausted by the system. Ensure unhindered air circulation. Allow
for air intake through base or door grids. Enable free air outlet via the upper cabinet cover
or a punched rear panel.
To ensure sufficient cooling make sure that there is free space above the system.
Protect the system from direct sunlight and direct contact with water.
The temperature of the interior must not fall below or exceed 0°C ... 50°C (derating >40°C:
2.5%/K).
Humidity must not fall below or exceed 5% ... 95%.

Bekijk gratis de handleiding van Phoenix Contact CHARX PS/3AC/920DC/87.5KW, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkPhoenix Contact
ModelCHARX PS/3AC/920DC/87.5KW
CategorieNiet gecategoriseerd
TaalNederlands
Grootte6956 MB