Diagnostics in the Axioline F system
8663_en_08 Phoenix Contact 17 / 38
2.3.2 Diagnostic parameter registers
The diagnostic parameter registers are always written to when a malfunction occurs and
whenever one of the error bits (F_PW_BIT, F_PF_BIT, F_BUS_BIT, F_CTRL_BIT) is set.
Otherwise, the diagnostic parameter registers have the value 0000
hex
.
When the aforementioned error bits are set, the diagnostic parameter registers provide
additional information on the status indicated in the diagnostic status register.
Diagnostic parameter register 1 contains the error code.
For an overview of the error codes, please refer to Section 3, “Error codes”.
Diagnostic parameter register 2 contains additional information. For localized bus or I/O
errors, this is the error location or the device number. The error location is stored as a slot
number. This starts at 1 and corresponds to the sequential number of the Axioline F mod-
ules that are installed one after another.