UM EN AXL F SYS DIAG
16 / 38 Phoenix Contact
8663_en_08
Status displays
The Ready, Active, and Run status displays indicate the current state of the system. The
diagnostic parameter registers are not used.
Following initialization, the driver is ready to operate. The Ready indicator bit is set
(F_READY_BIT = 1).
If the driver has been configured and a configuration frame has been activated without
errors, the system indicates that it is active. The Ready and Active indicator bits are set
(F_READY_BIT = 1, F_ACTIVE_BIT = 1).
In addition, the Run indicator bit is set (F_READY_BIT = 1, F_ACTIVE_BIT = 1, and
F_RUN_BIT = 1) when data exchange is started.
Error indicators
The PF, BUS, CTRL, and SYNC error indicators report an error, while PW reports a warning.
Errors which are indicated with BUS or CTRL will cause the bus to be disconnected. The
Run indicator bit is reset (F_RUN_BIT = 0).
Further information on the error cause is provided by the two diagnostic parameter reg-
isters.
If several error bits are 1 at the same time, the values in the parameter registers repre-
sent the error with the highest priority.
If there are I/O errors (PF= peripheral fault) at several devices, the parameter registers
show the message that occurred first. When you remove this message, the next pending
massage with the lowest device number is shown.
If there are I/O warnings (PW = peripheral warning) from several devices, the warnings
are shown in the same way as the I/O errors.
After an error has been removed or disappears (e.g., elimination of an interruption), the
bus is started again automatically and the output data is enabled again. The Run indicator
bit is set again (F_RUN_BIT = 1).
Table 2-9 Priorities of the error messages
Message Priority
CTRL 1 (highest priority)
BUS 2
SYNC 3
PF 4
PW 5 (lowest priority)