Testing using the PAT250SX
6. Testing using the PAT250SX
6.1 Class 1 test using substitute leakage @ 40 V AC
1. Plug the appliance
under test into the
PAT
2. Turn on the
appliance
under test
3. Connect BOND
lead P1 to a metal
point on the
appliance
4. Select required
voltage
Class 1 @ 500 V
OR
Class 1 @ 250 V for IT equipment
>2 s
5. Ensure probe (P1)
is connected
6. Remove probe
(P1)
7. 8. Class 1 Pass
NOTE : If the contact symbol is displayed during the test, the PAT has detected an open circuit load.
Ensure the appliance is switched on then press the Class 1 icon
NOTE : The PAT250SX performs various pre-checks prior to testing to ensure the asset is not short-circuit
and is switched on.