Testing with the EVX
6.4 Testing for PE earthing issues
The PE error function detects the presence of earthing issues through the EV charger that can
affect the safe use of the MFT-X1.
To test for PE errors ensure:
1. The EVX100 is connected to the MFT-X1 and communications have been established as
above and the charger is in charging state C.
2. Switch the MFT-X1 to the Loop impedance mode.
3. Switch Hot key 5 to the L-PE option.
4. Ensure the display shows the presence of 230 V AC on the voltage widget triangle.
5. Touch, but DO NOT PRESS, one of the red TEST buttons. If an issue exists with the PE
bonding the MFT-X1 shall display the PE warning as below and the test will not run.
PE warning
No warning symbol indicates it is safe to proceed with live testing.
NOTE : The PE inhibit function can be disabled in SETTINGS by setting the PE Confirmation to
OFF. However, the warning will always be displayed.
6.5 Testing loop impedance
Loop impedance is tested in the same way as on the standard MFT-X1 without the EVX
adaptor. For full details of loop impedance testing refer the full MFT-X1 user manual.
The EVX100 limits functionality to those tests suitable for use on an EV charger, as below: