Megger EVX100 handleiding
Handleiding
Je bekijkt pagina 15 van 24

www.megger.com EVX100
15
Testing with the EVX
6.6 Hot key options available with the EVX100:
Hot key options available are:
Hot key 1: Z: Shows the loop impedance value for the connection selected on hot
key 5
Zmax: Shows the latest loop impedance value and also the highest value
recorded if more than one measurement is made
Zref: Used to remove loop impedance values such as Ze from the
measured value.
Vdrop: Used with Zref and I-Vdrop settings to measure the volt-drop at the
charger under full load conditions.
Hot key 2: Select between the RCD protection type fitted to the EV charger. These are:
RDC EV: Used for testing L-PE circuits on chargers fitted with an RDC-DD device
RCD: Use for testing L-PE circuits protected by a type B RCD.
NO RCD: Used for all other connection options, L1-N, L2-N, L1-L2, L1-L3, L2-L3,
where tripping an RCD is not possible.
Hot key 3: Displays the connection recommendations and invalid test chart for Hot key 2 and Hot
key 5 combinations.
Hot key 4: Select either:
3 wire: (recommended for L-PE testing) or
2 wire: For all other loop test options
Hot key 5: The connection options for testing loop impedance on a charger are:
L1-PE, L1-N, L2-PE, L2-N, L3-PE, L3-N, L1-L2, L1-L3 or L2-L3.
Bekijk gratis de handleiding van Megger EVX100, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
Merk | Megger |
Model | EVX100 |
Categorie | Niet gecategoriseerd |
Taal | Nederlands |
Grootte | 3687 MB |