www.megger.com EVX100
15
Testing with the EVX
6.6 Hot key options available with the EVX100:
Hot key options available are:
Hot key 1: Z: Shows the loop impedance value for the connection selected on hot
key 5
Zmax: Shows the latest loop impedance value and also the highest value
recorded if more than one measurement is made
Zref: Used to remove loop impedance values such as Ze from the
measured value.
Vdrop: Used with Zref and I-Vdrop settings to measure the volt-drop at the
charger under full load conditions.
Hot key 2: Select between the RCD protection type fitted to the EV charger. These are:
RDC EV: Used for testing L-PE circuits on chargers fitted with an RDC-DD device
RCD: Use for testing L-PE circuits protected by a type B RCD.
NO RCD: Used for all other connection options, L1-N, L2-N, L1-L2, L1-L3, L2-L3,
where tripping an RCD is not possible.
Hot key 3: Displays the connection recommendations and invalid test chart for Hot key 2 and Hot
key 5 combinations.
Hot key 4: Select either:
3 wire: (recommended for L-PE testing) or
2 wire: For all other loop test options
Hot key 5: The connection options for testing loop impedance on a charger are:
L1-PE, L1-N, L2-PE, L2-N, L3-PE, L3-N, L1-L2, L1-L3 or L2-L3.