Megger EVX100 handleiding
Handleiding
Je bekijkt pagina 11 van 24

www.megger.com EVX100
11
Testing the EV charger
5. Testing the EV charger
The EVX100 takes control of the Control Pilot during the testing process. The operator has no
need to manually change the Control Pilot status, other than when performing Control Pilot
error testing.
The Proximity Pilot (PP) is set to 13 A for all testing purposes.
NOTE : To simplify the testing process the EVX automatically disables functionality not available
through the adaptor. These are: Insulation, continuity, current clamp and Earth testing.
5.1 Connecting the EVX adaptor and power ON/OFF
Ensure the EVX100 shows no sign of damage to the case or connection cable.
1. Insert the EVX adaptor to the MFT-X1.
The adaptor will only fit in one
orientation. Do not force the adaptor,
but be aware that it is a snug fit.
2. Connect the EVX connector plug to the EV charger. The EVX100 is now ready to establish
communications with the EV Charger.
3. Turn the left rotary dial on the MFT-X1 to
the Voltage setting.
NOTE : This will also switch on the EVX100
and the EV charger.
4. On the EVX100, the top LED will flash yellow. This indicates that the EVX100 is
establishing communications with the MFT-X1.
5. After a few seconds the LED will stop flashing yellow, indicating successful connection to
the MFT-X1.
Bekijk gratis de handleiding van Megger EVX100, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
Merk | Megger |
Model | EVX100 |
Categorie | Niet gecategoriseerd |
Taal | Nederlands |
Grootte | 3687 MB |