Technical Manual
CO2 / VOC Combi Sensor 55 [SCN-CO2MGS.02]
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 • Germany
Phone: +49-2263-880 • knx@mdt.de • www.mdt.de
63
63
The "Delay time" has the effect that the action to be carried out after opening/closing the window
only takes place after a configurable time. This means that a short opening of the window can be
carried out without influencing the control.
With "Action when closing the window" it can be set whether after closing, the window returns to
the mode before the lock or in the mode that, for example, was sent during the lock as from a timer
or a visualization.
The "Release time" defines the time after which the controller automatically returns to the
previous operating mode after the window has been opened. This is useful if, for example, you
forget to close the window again. In this case, the room would be prevented from cooling down in
winter or overheating in summer.
The following table shows the associated communication object:
Number
Name/Object function
Length
Usage
88
Temperature controller –
Window contact –
0=closed / 1=open /
1=closed / 0=open
1 Bit
Receiving the current window status.
Polarity depending on parameter setting.
Table 63: Communication object – Window contact