4.4.12 Window contact
The following settings are available for this parameter:
Figure 33: Settings Window contact
The setting options for this parameter are shown in the table below:
ETS-Text
Dynamic range
[Default value]
Comment
Window contact
not active
active
Setting whether window contact is
monitored or not.
State of window
0=closed / 1=open
(standard DPT)
1=closed / 0=open
Setting the polarity with which
value the window is open/closed.
Delay time
0 … 240 s
[5 s]
Setting of a time by which the
switching is delayed after
opening/closing the window.
Action when opening
the window
force Frost-/Heat protection
Fixed text.
Not changeable.
Action when closing
the window
HVAC Modus before locking
HVAC Modus catch up
Specify whether to switch to the
mode before the lock after closing
the window or to a new mode
changed during the lock.
Release time
not active (not recommended)
1 h 24 h
[12 h)]
Setting after which time the unit
automatically switches back to the
previous mode.
Table 62: Settings Window contact
With this function, the control in a room can be forced into frost or heat protection after opening a
window. Normal Heating/Cooling operation is thus interrupted for a long time. This prevents, for
example, that energy is unnecessarily consumed for heating after opening a window in winter. After
closing the window, it is then possible to switch back to normal operation.