Technical Manual
Motion Detector/Automatic Switch 55/63 [SCN-BWM55/63(T)(06).x2]
State 07/2025 - Version 1.4
4.3.2.5 Basic function: Send state
Single-button function
Withthisfunction,xedvaluescanbesentforapressedbutton(risingedge)andareleasedbutton(falling
edge).
The following table shows the available settings::
ETS Text
Dynamic range
[Default value]
Comment
Value for pressed button OFF
ON
Denesthesendbehaviourofthebutton.
Value for released button OFF
ON
Denesthesendbehaviourofthebutton.
Cyclic sending not active
active
Setting whether the value is sent cyclically.
Send cyclically every ... 1 s ... 3000 s
[300 s]
Setting the sending interval.
Only if “Cyclic sending” is active.
Send state after bus
power return
not active
active
Setting to specify whether the current state
is sent after bus power return.
Table 60: Settings – Single-button function: Send state
The following table shows the associated communication objects:
No. Name/Object function Length Usage
131 Button left – Send state 1 Bit Sends the respective value when the button is
pressed and released.
+5 Button right ...
Table 61: Communication objects – Single-button function: Send state