KIBXX II/KWIBXX II ICEBERG SERIES SYSTEMS KWIKOOL
21
FAULT
POSSIBLE CAUSE
POSSIBLE SOLUTION
Audible alarm fails to
clear on start up or
while operating
(KIB120XX II Only).
Iceberg Series
System displays FD.
Microprocessor has
detected fault with the
system VFD.
View fault code displayed on the system VFD,
located in the evaporator access door
Call 1-800-594-5665 (1-800-KWIKOOL) for
guidance.
Control board
displays FL.
Microprocessor has
detected Filter counter time
has elapsed (customer
controlled parameter)
Factory default settings is
30 days.
Replace air filters and reset counter.
Note
FL only alerts operators of the condition;
the system will not shut down during this
alarm.
System is ON and
display is showing
ON but Iceberg
Series System is not
supplying
conditioned air.
System is in time out (F
or C is flashing).
Control is set above
room temperature.
Control is adjusted out
of operating
parameters.
Not in the correct
operational MODE.
Wait 2 minutes for the time delay to elapse.
Review System Operations guide, Mode &
temperature settings. Call 1-800-594-5665 (1-800-
KWIKOOL) for guidance.
System is ON but
the microprocessor
board resets the
time delay (flashing
F or C) when the
compressor
attempts to start.
Microprocessor board
detects voltage drop below
operating parameters.
Confirm the integrity of the source power.
Check for proper wire size and length of power
extension cable.
Be sure the circuit is dedicated to only the
operation of the KwiKool.
Call 1-800-594-5665 (1-800-KWIKOOL) for
guidance.
Power is supplied
but control is blank.
Low voltage circuit is not
engaged
Check source power breaker and verify incoming
power to connector. Reset switch on low voltage
transformer in KWIB & KIB120XX II systems. Call
1-800-594-5665 (1-800-KWIKOOL) for guidance.
System trips breaker
on start up.
Incoming power is
incorrect. Breaker is
undersized or faulty and/or
power cable is too long
and/or undersized.
Verify the circuit and power cable is within the
systems specifications. Consult with the
electrician.
Call 1-800-594-5665 (1-800-KWIKOOL) for
guidance.
System starts up
and cools, but the
Condenser
Discharge air
exhaust fan ramps
up and slows down
or the condenser
discharge fan stops
and starts.
Normal operating condition
especially in low
temperatures. Only the
KIB120XX II or other
Iceberg Series Systems
with optional ultra-low
ambient temperature
controls ramps up and
slows down. All other
models stop and start.
No action required, see sections IV C. 2.
NOTE
To avoid excessive fan cycling, Discharge
Return air must not be below the
specifications of the Iceberg system