FAULT 
POSSIBLE CAUSE 
POSSIBLE SOLUTION 
Audible alarm fails to 
clear on start up or 
while operating 
(KIB120XX II Only). 
Iceberg Series 
System displays FD. 
Microprocessor has 
detected fault with the 
system VFD. 
View fault code displayed on the system VFD, 
located in the evaporator access door 
Call 1-800-594-5665 (1-800-KWIKOOL) for 
guidance. 
Control board 
displays FL. 
Microprocessor has 
detected Filter counter time 
has elapsed (customer 
controlled parameter) 
Factory default settings is 
30 days. 
Replace air filters and reset counter. 
Note 
FL only alerts operators of the condition; 
the system will not shut down during this 
alarm. 
System is ON and 
display is showing 
ON but Iceberg 
Series System is not 
supplying 
conditioned air. 
  System is in time out (F 
or C is flashing). 
  Control is set above 
room temperature. 
  Control is adjusted out 
of operating 
parameters. 
  Not in the correct 
operational MODE. 
Wait 2 minutes for the time delay to elapse. 
Review System Operations guide, Mode & 
temperature settings. Call 1-800-594-5665 (1-800-
KWIKOOL) for guidance. 
System is ON but 
the microprocessor 
board resets the 
time delay (flashing 
F or C) when the 
compressor 
attempts to start. 
Microprocessor board 
detects voltage drop below 
operating parameters. 
  Confirm the integrity of the source power. 
  Check for proper wire size and length of power 
extension cable. 
  Be sure the circuit is dedicated to only the 
operation of the KwiKool. 
Call 1-800-594-5665 (1-800-KWIKOOL) for 
guidance. 
Power is supplied 
but control is blank. 
Low voltage circuit is not 
engaged 
Check source power breaker and verify incoming 
power to connector. Reset switch on low voltage 
transformer in KWIB & KIB120XX II systems. Call 
1-800-594-5665 (1-800-KWIKOOL) for guidance. 
System trips breaker 
on start up. 
Incoming power is 
incorrect. Breaker is 
undersized or faulty and/or 
power cable is too long 
and/or undersized. 
Verify the circuit and power cable is within the 
systems specifications. Consult with the 
electrician. 
Call 1-800-594-5665 (1-800-KWIKOOL) for 
guidance. 
System starts up 
and cools, but the 
Condenser 
Discharge air 
exhaust fan ramps 
up and slows down 
or the condenser 
discharge fan stops 
and starts. 
Normal operating condition 
especially in low 
temperatures. Only the 
KIB120XX II or other 
Iceberg Series Systems 
with optional ultra-low 
ambient temperature 
controls ramps up and 
slows down. All other 
models stop and start. 
No action required, see sections IV C. 2. 
NOTE 
To avoid excessive fan cycling, Discharge 
Return air must not be below the 
specifications of the Iceberg system 