KWIKOOL KIBXX II/KWIBXX II ICEBERG SERIES SYSTEMS
22
FAULT
POSSIBLE CAUSE
POSSIBLE SOLUTION
Display shows 32
and Iceberg Series
System will not turn
on cooling.
No connection of
temperature sensor to
Microprocessor.
Temperature Sensor
malfunctions.
Call 1-800-594-5665 (1-800-KWIKOOL) for
guidance.
Supply airflow is
limited, and/or water
is dripping from the
front of the system.
Supply or Return air is
blocked or restricted,
and/or the evaporator coil is
freezing.
Verify that Supply and Return air are not
blocked and ductwork is installed to
specification.
Remove or add duct as needed.
Check air filter for blockage.
KWIB & KIB120XX II users check Supply air
fan for correct rotation and belt condition.
Refer to Appendix B.
Condensate is not
pumping.
Water is below pumping
level, external line
restricted, line installed with
too high a lift for the pump’s
capacity.
Reservoir fills, and then pumps. Check for line
crimping or restrictions and proper line run height.
Refer to the user guide Section 5: Built in
Safeguards.
Evaporator coil is
freezing
Low or restricted
airflow.
Undersized capacity.
Iceberg Series Cooler
constantly on, unable to
achieve set point.
Low return air
temperature out of
factory specifications.
Evaporator door open.
Mechanical system
malfunction.
Direct Supply Return air to area of highest heat
load.
Check for blocked airflow from the supply air.
Replace air filters.
Adjust set point to allow the Iceberg Series
System to cycle.
Add another Iceberg system or larger capacity
model.
Close evaporator compartment door.
Check for correct rotation and inspect drive
belts on KWIB & KIB120XX II systems supply
air blower for worn condition or breaking.
Install service gauges to view pressures.
Call 1-800-594-5665 (1-800-KWIKOOL) for
guidance.
Chatter or hum is
heard from the
control box while the
system is operating.
Incoming source power is
poor or low voltage
component is faulty.
Check for proper voltage selection on 208/230-volt
Iceberg Series Systems. Remove excess or
undersized power cable and check incoming
power. Call 1-800-594-5665 (1-800-KWIKOOL) for
guidance.
Discharge air
exhaust fan stops
and the system
alarms HP during
operation.
KIB120XX II only.
Condenser drive has
detected a fault with the
incoming electrical power
or is not receiving an
operating signal.
Check condenser motor drive (VFD) for trip. Reset
if needed. Make note of the displayed fault code
on the drive. Call 1-800-594-5665 (1-800-
KWIKOOL) for guidance.