KWIKOOL   KIBXX II/KWIBXX II ICEBERG SERIES SYSTEMS   
22 
FAULT 
POSSIBLE CAUSE 
POSSIBLE SOLUTION 
Display shows 32 
and Iceberg Series 
System will not turn 
on cooling. 
No connection of 
temperature sensor to 
Microprocessor. 
Temperature Sensor 
malfunctions. 
Call 1-800-594-5665 (1-800-KWIKOOL) for 
guidance. 
Supply airflow is 
limited, and/or water 
is dripping from the 
front of the system. 
Supply or Return air is 
blocked or restricted, 
and/or the evaporator coil is 
freezing. 
  Verify that Supply and Return air are not 
blocked and ductwork is installed to 
specification. 
  Remove or add duct as needed. 
  Check air filter for blockage. 
  KWIB & KIB120XX II users check Supply air 
fan for correct rotation and belt condition. 
Refer to Appendix B. 
Condensate is not 
pumping. 
Water is below pumping 
level, external line 
restricted, line installed with 
too high a lift for the pump’s 
capacity. 
Reservoir fills, and then pumps. Check for line 
crimping or restrictions and proper line run height. 
Refer to the user guide Section 5: Built in 
Safeguards. 
Evaporator coil is 
freezing 
  Low or restricted 
airflow. 
  Undersized capacity. 
  Iceberg Series Cooler 
constantly on, unable to 
achieve set point. 
  Low return air 
temperature out of 
factory specifications. 
  Evaporator door open. 
  Mechanical system 
malfunction. 
  Direct Supply Return air to area of highest heat 
load. 
  Check for blocked airflow from the supply air. 
  Replace air filters. 
  Adjust set point to allow the Iceberg Series 
System to cycle. 
  Add another Iceberg system or larger capacity 
model. 
  Close evaporator compartment door. 
  Check for correct rotation and inspect drive 
belts on KWIB & KIB120XX II systems supply 
air blower for worn condition or breaking. 
Install service gauges to view pressures. 
Call 1-800-594-5665 (1-800-KWIKOOL) for 
guidance. 
Chatter or hum is 
heard from the 
control box while the 
system is operating. 
Incoming source power is 
poor or low voltage 
component is faulty. 
Check for proper voltage selection on 208/230-volt 
Iceberg Series Systems. Remove excess or 
undersized power cable and check incoming 
power. Call 1-800-594-5665 (1-800-KWIKOOL) for 
guidance. 
Discharge air 
exhaust fan stops 
and the system 
alarms HP during 
operation. 
KIB120XX II only. 
Condenser drive has 
detected a fault with the 
incoming electrical power 
or is not receiving an 
operating signal. 
Check condenser motor drive (VFD) for trip. Reset 
if needed. Make note of the displayed fault code 
on the drive. Call 1-800-594-5665 (1-800-
KWIKOOL) for guidance. 