KWIKOOL KIBXX II/KWIBXX II ICEBERG SERIES SYSTEMS
20
FAULT
POSSIBLE CAUSE
POSSIBLE SOLUTION
Iceberg Series
System Displays
HP. Audible alarm is
sounding during
start up or while
operating.
Microprocessor board has
detected high pressure.
The High Pressure switch
is tripped.
High-pressure trip is normally caused by reduced
or stopped Condenser Air flow on KIBXX II, or
water flow on KWIBXX II.
Check for restriction in ducting on air-cooled
systems or restrictions in water line sets on
water-cooled systems.
Check for Condenser Air system ventilation
(See Section II. C. 4) or source water input on
KWIBXX II.
For KIBXX II, check condenser motors and/or
blowers for proper operation.
On KIB12023 II or KIB12043 II check VFD
(motor drive) for trip. Reset if necessary.
High-pressure reset switch is a manual reset
type. To reset, open filter door. The button is
located above the filter. Press button to reset
(the operator should feel a click).
Iceberg Series
System Displays LP
(Low Pressure
(Freon)), Audible
alarm is sounding
during start up or
while operating.
Microprocessor board has
detected low pressure. This
alarm may cycle on and off.
Check air filter and replace if dirty.
Make sure nothing is blocking the filter inlet.
Check for icing on coil.
Resets automatically when fault condition is
corrected.
Call 1-800-594-5665 (1-800-KWIKOOL) for
guidance if condition continues.
Iceberg Series
System Displays
PH, Audible alarm is
sounding during
start up.
Phase Monitor (if equipped)
has detected incoming
power issue on equipped
systems.
See Troubleshooting Guide for systems equipped
with a phase monitor (Appendix - Part B).
Audible alarm fails to
clear on start up or
while operating.
Iceberg Series
System displays FS.
Microprocessor has
detected freezing on the
evaporator coil if the
system has a factory
installed freeze sensor.
(Special order).
Check for freezing on the evaporator coil and turn
the system off to let it thaw out. Call 1-800-
KWIKOOL if the system is not equipped with a
freeze sensor. Auto resets upon correction.
Audible alarm fails to
clear on start up or
while operating.
Iceberg Series
System displays A1.
Microprocessor has
detected customer installed
normally closed circuit
open.
Review aftermarket device installed for fault that is
opening the circuit. Auto resets upon correction
Audible alarm fails to
clear on start up or
while operating.
Iceberg Series
System displays A2.
Microprocessor has
detected customer-installed
normally-open circuit
closed
Review aftermarket device installed for fault that is
closing the circuit. Auto reset upon correction.
Call 1-800-594-5665 (1-800-KWIKOOL) for
guidance.