Intergas Xtend Split handleiding
Handleiding
Je bekijkt pagina 65 van 88

65
The reduced temperature function via a room temperature setpoint can
be deactivated by setting P218 to ‘10ºC’ §11.4.1
► This function is intended for situations when the night-time
reduction is being used (P180 = 0).
► In situations where the same room temperature has been set 24/7,
the CH timed program can be used to indicated when the boiler
should be blocked. For the period of the CH mode OFF‘ timed
program, the reduced temperature function will be active.
At lower external temperatures, this function may have the opposite
eect: the room temperature will drop too much, even though it
is no longer possible to compensate for it. Using P216, a ‘reduced
temperature o’ temperature can be set.
11.5 Room heating settings (CH mode)
The hybrid system is controlled using the Intergas Comfort Touch
thermostat or any OpenTherm thermostat. Parameter P202 is set to
‘4’, the default value for the this type of thermostat.
There are several other control modes available in addition to the
factory settings, which can even be combined with each other. These
are divided into internal and external control modes.
Internal control modes are based on the supply temperature. The
system uses a weather-dependent control (WDC) setting that adjusts
based on the external temperature and the set heating curve.
Optional accessories, such as the external sensor T42 (outdoor) and
remote temperature sensor T43 (system flow), are important for
optimal system performance.
External control modes use an external thermostat to determine the
supply temperature. There are also ON/OFF CH modes. These fall
under the external control modes.
If these are being used for a dierent application (dierent from the
default value), further information can be requested from Intergas
Heating Ltd.
Bekijk gratis de handleiding van Intergas Xtend Split, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
| Merk | Intergas |
| Model | Xtend Split |
| Categorie | Niet gecategoriseerd |
| Taal | Nederlands |
| Grootte | 11570 MB |