Delay time (Min.)
Outside temperature (ºC)
P114
P113
P115 P116
Activating the boiler is determined based on the water temperature
and room temperature (using OpenTherm if available).
Generally, this setting works using degree minutes. This means that a
significant deviation in water temperature leads to the involvement of
the boiler sooner than a minor deviation.
Using P107, the activation threshold can be set. At a lower value, the
boiler will be involved more quickly.
Heat pump malfunction
If the heat pump is unavailable due to a malfunction, the boiler will be
activated directly to meet the heating demand. The delay time can be
set using P108.
Delay time before the involvement of the boiler aer initiating
heating
When the heating phase is initiated, the involvement of the boiler
can be postponed in order to allow the heat pump time to achieve
the desired heat on its own. A wait time that depends on the external
temperature can be set for this. In relatively warm weather, the wait
time can be extended.
Using P113, a minimum external temperature can be set
(the default is 0 ºC).
Using P114, a maximum external temperature can be set
(the default is 20 ºC).
Using P115, the wait time can be set for a low external temperature
(the default is 5 min).
Using P116, the wait time can be set for a high external temperature
(the default is 50 min).
11.4 Settings for activating the boiler
11.4.1 Setting a reduced temperature
During a period in the daytime, boiler involvement can be
postponed, which will result in a lower room temperature.
This ‘reduced temperature’ can based on a ‘reduced room
temperature setpoint’ or a timed program.
Reduced temperature setpoint.
Using P218, a temperature setpoint can be set. If the room
temperature setpoint is actually set to be equal to or lower
than this value, the reduced temperature function will activate.
When the reduced temperature function is active, the boiler
is prevented from being involved. This allows the room
temperature to drop below the setpoint. A maximum drop
in temperature can be set using P219. If the current room
temperature drops below the thermostat value (— negative)
P219 — then the boiler becomes free to activate.
4 = Maximum heat pump use
In this mode, the heat pump is used as much as possible, however
the boiler can be activated as well but only if the heat pump
cannot achieve the required target temperature.
5 = Only the boiler
If there are issues with the heat pump, the system can be forced to
use the boiler.