If the measured Humidity(PV) ≥ Humidity
Setting Value(HS)+Dehumidification
Differential Value(DD), the equipment will
enter dehumidification state, the green led
is on, WORK2 output socket turns on. If the
green led is blinking, indicating that the
dehumidification device is in the state of the
dehumidification delay protection, WORK2
output socket turns off. If the measured
Humidity(PV) ≤ Humidity Setting Value(HS),
the green led is off, WORK2 output socket
turns off.
Example: HS=50.0%RH, HD=5.0%RH,
DD=8.0%RH, If PV(the measured humidity)
≥ 58.0%RH(HS+DD), the equipment will
enter the dehumidification state, the green
led is on, WORK2 output socket turns on. If
PV ≤ 55.0%RH(HS), the green led is off,
WORK2 output socket turns off. If PV ≤
45.0%RH (HS-HD), the equipment will enter
the humidification state, the red led is on,
WORK1 output socket turns on. If PV ≥
50.0%RH(HS), the red led is off, WORK1
output socket turns off.
Note: There is no need to judge the
differential value of humidification or
dehumidification when power on or exiting
the setting state. For example: when power
on or exiting the setting state HS=50.0%RH,
HD=5.0%RH, DD=8.0%RH. If PV(the
measured humidity) > 50.0%RH(HS), it will
enter the dehumidification state. When PV ≤
50.0%RH(HS), the dehumidification stops,
then return to normal humidity control
mode. If PV < 50.0%RH, it will enter the
11
If the measured Humidity(PV) ≥ Humidity
Setting Value(HS)+Dehumidification
Differential Value(DD), the equipment will
enter dehumidification state, the green led
is on, WORK2 output socket turns on. If the
green led is blinking, indicating that the
dehumidification device is in the state of the
dehumidification delay protection, WORK2
output socket turns off. If the measured
Humidity(PV) ≤ Humidity Setting Value(HS),
the green led is off, WORK2 output socket
turns off.
Example: HS=50.0%RH, HD=5.0%RH,
DD=8.0%RH, If PV(the measured humidity)
≥ 58.0%RH(HS+DD), the equipment will
enter the dehumidification state, the green
led is on, WORK2 output socket turns on. If
PV ≤ 55.0%RH(HS), the green led is off,
WORK2 output socket turns off. If PV ≤
45.0%RH (HS-HD), the equipment will enter
the humidification state, the red led is on,
WORK1 output socket turns on. If PV ≥
50.0%RH(HS), the red led is off, WORK1
output socket turns off.
Note: There is no need to judge the
differential value of humidification or
dehumidification when power on or exiting
the setting state. For example: when power
on or exiting the setting state HS=50.0%RH,
HD=5.0%RH, DD=8.0%RH. If PV(the
measured humidity) > 50.0%RH(HS), it will
enter the dehumidification state. When PV ≤
50.0%RH(HS), the dehumidification stops,
then return to normal humidity control
mode. If PV < 50.0%RH, it will enter the
If the measured Humidity(PV) ≥ Humidity
Setting Value(HS)+Dehumidification
Differential Value(DD), the equipment will
enter dehumidification state, the green led
is on, WORK2 output socket turns on. If the
green led is blinking, indicating that the
dehumidification device is in the state of the
dehumidification delay protection, WORK2
output socket turns off. If the measured
Humidity(PV) ≤ Humidity Setting Value(HS),
the green led is off, WORK2 output socket
turns off.
Example: HS=50.0%RH, HD=5.0%RH,
DD=8.0%RH, If PV(the measured humidity)
≥ 58.0%RH(HS+DD), the equipment will
enter the dehumidification state, the green
led is on, WORK2 output socket turns on. If
PV ≤ 55.0%RH(HS), the green led is off,
WORK2 output socket turns off. If PV ≤
45.0%RH (HS-HD), the equipment will enter
the humidification state, the red led is on,
WORK1 output socket turns on. If PV ≥
50.0%RH(HS), the red led is off, WORK1
output socket turns off.
Note: There is no need to judge the
differential value of humidification or
dehumidification when power on or exiting
the setting state. For example: when power
on or exiting the setting state HS=50.0%RH,
HD=5.0%RH, DD=8.0%RH. If PV(the
measured humidity) > 50.0%RH(HS), it will
enter the dehumidification state. When PV ≤
50.0%RH(HS), the dehumidification stops,
then return to normal humidity control
mode. If PV < 50.0%RH, it will enter the
If the measured Humidity(PV) ≥ Humidity
Setting Value(HS)+Dehumidification
Differential Value(DD), the equipment will
enter dehumidification state, the green led
is on, WORK2 output socket turns on. If the
green led is blinking, indicating that the
dehumidification device is in the state of the
dehumidification delay protection, WORK2
output socket turns off. If the measured
Humidity(PV) ≤ Humidity Setting Value(HS),
the green led is off, WORK2 output socket
turns off.
Example: HS=50.0%RH, HD=5.0%RH,
DD=8.0%RH, If PV(the measured humidity)
≥ 58.0%RH(HS+DD), the equipment will
enter the dehumidification state, the green
led is on, WORK2 output socket turns on. If
PV ≤ 55.0%RH(HS), the green led is off,
WORK2 output socket turns off. If PV ≤
45.0%RH (HS-HD), the equipment will enter
the humidification state, the red led is on,
WORK1 output socket turns on. If PV ≥
50.0%RH(HS), the red led is off, WORK1
output socket turns off.
Note: There is no need to judge the
differential value of humidification or
dehumidification when power on or exiting
the setting state. For example: when power
on or exiting the setting state HS=50.0%RH,
HD=5.0%RH, DD=8.0%RH. If PV(the
measured humidity) > 50.0%RH(HS), it will
enter the dehumidification state. When PV ≤
50.0%RH(HS), the dehumidification stops,
then return to normal humidity control
mode. If PV < 50.0%RH, it will enter the
Bekijk gratis de handleiding van Inkbird IHC-200-WIFI, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.