IFM SUH251 handleiding
Handleiding
Je bekijkt pagina 37 van 45

Ultrasonic flow meter without display SUHxxx
© ifm electronic gmbh 11661449 / 01 07 / 2025 37
10.4.3 Operating hours counter
The operating hours since the first set-up are stored by the unit.
The current value can be read via the IO-Link interface.
The counter cannot be reset.
10.4.4 Internal temperature
The sensor measures the internal temperature.
The current value can be read via the IO-Link interface.
10.4.5 Signal quality
The signal quality of the sensor can be affected by irregularities in the medium (e.g. strong turbulences, air
bubbles, particles or build-up).
The unit detects the signal quality in three stages:
Signal quality Explanation
Normal
The unit operates without restrictions (normal operation).
Low
The signal quality is disturbed, but the unit is still working within its specifications.
No signal
No medium is present or no signal can be created.
The current value can be read via the IO-Link interface.
In addition, the signal quality can be indicated via a switching signal.
Switching signal for signal quality [ 23]
10.5 Service functions
10.5.1 Device information
Unalterable device information is stored on the unit. This includes:
▪ Product name
▪ Product family
▪ Manufacturer
▪ Manufacturer ID
▪ Device ID
▪ Serial number
▪ Hardware / firmware revision
▪ Description
In addition, further freely definable tags with a maximum length of 32 characters can be assigned to the
unit via the IO-Link interface using suitable parameter setting software. This includes:
▪ application-specific tag
▪ function tag
▪ location tag
Bekijk gratis de handleiding van IFM SUH251, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
Merk | IFM |
Model | SUH251 |
Categorie | Niet gecategoriseerd |
Taal | Nederlands |
Grootte | 3640 MB |