IFM SUH251 handleiding
Handleiding
Je bekijkt pagina 38 van 45

SUHxxx Ultrasonic flow meter without display
38 © ifm electronic gmbh 11661449 / 01 07 / 2025
10.5.2 Simulation
With this function, process values are simulated and their signal path is checked.
Process values that lead to an error message or warning can be simulated (e.g. OL).
When the simulation is started, the values of the totaliser are frozen and the simulated totaliser is set to 0.
The simulated flow value then has an effect on the simulated totaliser. When the simulation is ended, the
initial totaliser values are restored.
During the simulation:
▪ The simulation has no effect on the current process values. The outputs operate as previously set.
▪ The original totaliser value remains saved without any changes even if there is a real flow.
▪ No error messages of the current application are available. They are suppressed by the simulation.
The following values can be simulated:
▪ process values for flow and temperature
▪ process values outside the measuring range (cr.UL, UL, OL, cr.OL)
Parameters to be set:
S.Tim; S.FLW; S.TMP
Bekijk gratis de handleiding van IFM SUH251, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
Merk | IFM |
Model | SUH251 |
Categorie | Niet gecategoriseerd |
Taal | Nederlands |
Grootte | 3640 MB |