Electronic manometer PG17xx
33
10.3.1.1 Parameter setting via device keys: Switching signal
Switching signal channel SSC1.1 is set using the device keys. Further switching signal channels
can be set via the IO-Link interface.
ü The standard unit of measurement is selected: [EF] > [CFG] > [uni.P].
ü Switching channel SSC1.1 is selected for output 1: [EF] > [OU1] > [ou1] = [SSC1].
u Go to [EF] > [OU1] to configure output OUT1.
Single point mode:
u Select [ModE] and set the switch-point mode: [1-P].
u Select [SP1] and set switch point 1.
u Select [HYSt] and set the hysteresis.
Two-point mode:
u Select [ModE] and set the switch-point mode: [2-P].
u Select [SP1] and set switch point 1.
u Select [SP2] and set switch point 2.
Window mode:
u Select [ModE] and set the switch-point mode: [WInd].
u Select [SP1] and set switch point 1.
u Select [SP2] and set switch point 2.
u Select [HYSt] and set the hysteresis.
10.3.1.2 Teach via device keys: Switching signal
Switching signal channel SSC1.1 is set using the device keys. Further switching signal channels
can be set via the IO-Link interface.
ü The standard unit of measurement is selected: [EF] > [CFG] > [uni.P].
ü Switching channel SSC1.1 is selected for output 1: [EF] > [OU1] > [ou1] = [SSC1].
u Go to [EF] > [OU1] to configure output OUT1.
Single point mode:
u Select [ModE] and set the switch-point mode: [1-P].
u Approach the system pressure at which the output is to switch and keep it constant.
u Select [tSP1] and set [Yes].
w The current value minus the hysteresis is adopted as switch point SP1.
u Select [HYSt] and set the hysteresis.
Two-point mode:
u Select [ModE] and set the switch-point mode: [2-P].
u Approach the system pressure at which the output is to switch and keep it constant.
u Select [tSP1] and set [Yes].
w The current value is adopted as switch point SP1.
u Approach the system pressure at which the output is to reset and keep it constant.
u Select [tSP2] and set [Yes].
w The current value is adopted as switch point SP2.