IFM AL4242 handleiding
Handleiding
Je bekijkt pagina 45 van 82

Remote I/O module 8DO 8DI AL4242
45
Name Description Value range Access
[bootloaderrevision] Bootloader version E.g. AL4xxx_bl_1.4.0.39 ro
1
[fieldbustype] Fieldbus ModbusTCP ro
1
1
Read only
Requirements:
ü IoT Core Visualizer has been started.
ü The [Parameter] menu is active.
u Select the [deviceinfo] submenu.
w The menu page shows device information.
9.2.3.7 Reading the firmware version
Available information:
Name Description Value range Access
[version] Firmware version AL4x4x_fw_md_1.4.0.142 ro
1
[type] Type • firmware: Firmware type ro
1
1
Read only
Requirements:
ü IoT Core Visualizer has been started.
ü The [Parameter] menu is active.
u Select the [firmware] submenu.
w The menu page shows the available information.
9.2.3.8 Setting the application tag
Available parameters:
Name Description Value range Access
[applicationtag] Device designation in monitoring software E.g. “factory 2 plant 1” rw
1
1
Read and write
32 bytes are available on the device for storing the applicationtag parameter. If the memory
range is exceeded, the device will abort the write process (diagnostic code 400).
u When writing the applicationtag parameter, observe the different memory requirements
of the individual UTF-8 characters (characters 0-127: 1 byte per character; character >127:
more than 1 byte per character).
Requirements:
ü IoT Core Visualizer has been started.
ü The [Parameter] menu is active.
u Select the [devicetag] submenu.
w The menu page shows the current settings.
u Enter the application tag.
u Click on to save the changes to the device.
w The new application tag is set.
Bekijk gratis de handleiding van IFM AL4242, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
| Merk | IFM |
| Model | AL4242 |
| Categorie | Niet gecategoriseerd |
| Taal | Nederlands |