IFM AL4143 handleiding

62 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 20 van 62
AL4143 Remote I/O module 16 DI
20
-40 -30 -20 -10 0 10 20 30 40 50 60 70
1
2
3
4
2000 m
Current [A]
Temperature [°C]
0.5
1.5
2.5
3.5
1
1: I
US
at ports X1…X8
-40 -30 -20 -10 0 10 20 30 40 50 60 70
2
4
6
8
10
12
14
16
18
2000 m
Current [A]
Temperature [°C]
2
1
1: I
UA-daisy-chain
at port XD2
2: I
US-daisy-chain
at port XD2
Example:
Temperature I
UA-daisy-chain
(XD2) I
USmax
(XD1) I
US
(X1…X8) I
US-daisy-chain
(XD2)
50°C 11.2A 11.0A 2.6A 8.4A
6.6 Voltage output
An additional device can be supplied via the power OUT port (daisy chain). The supply voltages US
and UA are looped through from port XD1 to port XD2.
Max. current of US: 15.9 A (for UL applications: 10.8A)
Max. current of UA: 16 A (for UL applications: 14A)
Wiring:
u Optional: Connect an additional device to port XD2.
u For connection, use an L-coded M12 connector (with at least protection rating: IP65 / IP66 / IP67 /
IP69K).
u Tighten the cable plug using 1.3 ± 0.1Nm.
u Observe the derating behaviour of the device (Ò Derating behaviour/18)!