-40 -30 -20 -10 0 10 20 30 40 50 60 70
1
2
3
4
2000 m
Current [A]
Temperature [°C]
0.5
1.5
2.5
3.5
1
1: I
US
at ports X1...X8
6.5.1.2 Derating with daisy chain
-40 -30 -20 -10 0 10 20 30 40 50 60 70
1
2
3
4
2000 m
3000 m
4000 m
Current [A]
Temperature [°C]
0.5
1.5
2.5
3.5
1
1: I
US
at ports X1…X8
-40 -30 -20 -10 0 10 20 30 40 50 60 70
2
4
6
8
10
12
14
16
18
2000 m
3000 m
4000 m
Current [A]
Temperature [°C]
2
1
1: I
UA-daisy-chain
at port XD2
2: I
US-daisy-chain
at port XD2
Example: derating (2000m)
Temperature I
UA-daisy-chain
(XD2) I
USmax
(XD1) I
US
(X1…X8) I
US-daisy-chain
(XD2)
30°C 16 A 15.9 A 3.9 A 12 A
30°C 0 A 15.9 A
30°C 1.8 A 14.1 A
60°C 8 A 8 A 2 A 6 A
60°C 0 A 8 A
60°C 1 A 7 A
Explanation: The current I
USmax
at port XD1 is the sum of the currents I
US
taken from ports X1…X8 and
the current I
US-daisy-chain
taken from port XD2 for the supply of further devices.
Formula: I
USmax
(XD1) = I
US
(X1…X8) + I
US-daisy-chain
(XD2)
The less current is consumed at ports X1...X8, the more current will be available to supply further
devices via daisy chain through port XD2.
For UL applications:

Bekijk gratis de handleiding van IFM AL4143, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkIFM
ModelAL4143
CategorieNiet gecategoriseerd
TaalNederlands
Grootte5317 MB