AL4143 Remote I/O module 16 DI
18
CAUTION
Exceeding the maximum input current of 16A
w Risk of fire
u Dimension the I
U
and I
A
of the US and UA supply voltages accordingly, taking into
account the derating behaviour of the device: Derating behaviour (Ò/18)
Wiring:
3
1 4
2
5
1: L+ (US)
2: L- (UA)
3: L- (US)
4: L+ (UA)
5: FE
u Disconnect power.
u Connect the device via the XD1 port to the US supply voltage with 24VDC (20...28V PELV).
u Optional: Connect the device via the XD1 port to the UA supply voltage with 24VDC (20...28V
PELV).
u For connection, use an L-coded M12 connector (with at least protection rating: IP65 / IP66 / IP67 /
IP69K).
u Tighten the cable sockets according to the torque specifications indicated by the cable vendor.
Maximum permissible tightening torque: 0.8Nm
6.5.1 Derating behaviour
The current I
US
available at ports X1...X8 and the currents I
US-daisy-chain
and I
UA-daisy-chain
available at port
XD2 depend on the ambient temperature of the device.
6.5.1.1 Derating without daisy chain
-40 -30 -20 -10 0 10 20 30 40 50 60 70
1
2
3
4
2000 m
3000 m
4000 m
Current [A]
Temperature [°C]
0.5
1.5
2.5
3.5
1
1: I
US
at ports X1...X8
For UL applications: