IFM AL4143 handleiding
Handleiding
Je bekijkt pagina 18 van 62

AL4143 Remote I/O module 16 DI
18
CAUTION
Exceeding the maximum input current of 16A
w Risk of fire
u Dimension the I
U
and I
A
of the US and UA supply voltages accordingly, taking into
account the derating behaviour of the device: Derating behaviour (Ò/18)
Wiring:
3
1 4
2
5
1: L+ (US)
2: L- (UA)
3: L- (US)
4: L+ (UA)
5: FE
u Disconnect power.
u Connect the device via the XD1 port to the US supply voltage with 24VDC (20...28V PELV).
u Optional: Connect the device via the XD1 port to the UA supply voltage with 24VDC (20...28V
PELV).
u For connection, use an L-coded M12 connector (with at least protection rating: IP65 / IP66 / IP67 /
IP69K).
u Tighten the cable sockets according to the torque specifications indicated by the cable vendor.
Maximum permissible tightening torque: 0.8Nm
6.5.1 Derating behaviour
The current I
US
available at ports X1...X8 and the currents I
US-daisy-chain
and I
UA-daisy-chain
available at port
XD2 depend on the ambient temperature of the device.
6.5.1.1 Derating without daisy chain
-40 -30 -20 -10 0 10 20 30 40 50 60 70
1
2
3
4
2000 m
3000 m
4000 m
Current [A]
Temperature [°C]
0.5
1.5
2.5
3.5
1
1: I
US
at ports X1...X8
For UL applications:
Bekijk gratis de handleiding van IFM AL4143, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
Merk | IFM |
Model | AL4143 |
Categorie | Niet gecategoriseerd |
Taal | Nederlands |
Grootte | 5317 MB |