Remote I/O module 16 DI AL4043
33
Name Description Value range Access
[configuration] > [byteswap] Arrangement of the bytes in a data word • big-endian: Big-endian format
• little-endian: Little-endian
format
rw
1
1
Read and write
2
Read only
Requirements:
ü IoT Core Visualizer has been started.
ü The [Parameter] menu is active.
u Select the [fieldbussetup] > [configuration] submenu.
u Select the [fieldbussetup] > [network] submenu.
w The menu page shows the current settings.
u Set the parameters.
u Click on to save the changes to the device.
u If necessary, restart the device.
w The ModbusTCP interface is configured.
9.2.3.2 Configuring input filters
u Observe the notes on input filters: Digital input filters (Ò/8)
Available parameters:
Name Description Value range Access
[debounce_time] Debounce time (= value * 0.1milliseconds) • 0: 0ms (default)
…
• 500: 50 ms
rw
1
[hold_time] Hold time (= value * 0.1milliseconds) • 0: 0ms (default)
…
• 60000: 6000 ms
rw
1
[hold_level] Hold level • low: hold LOW
• high: hold HIGH (default)
rw
1
[invert] Inversion • signal not inverted: do not invert
(default)
• signal inverted: invert
rw
1
1
Read and write; parameter can only be changed if no connection to fieldbus controller is established
Requirements:
ü IoT Core Visualizer has been started.
ü The [Parameter] menu is active.
u Select submenu [io] > [port[n]] (n: 1...8).
w The menu page shows the current settings of the digital input filters on pin 2 and pin 4 of the
port.
u Set the parameters.
u Click on to save the changes to the device.
w The filters of the digital inputs are configured.