IFM AL4043 handleiding

59 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 32 van 59
AL4043 Remote I/O module 16 DI
32
9.2.3 Configuring the device
The [Parameter] menu page provides access to the configuration options of the device.
The configuration created via the IoT Core Visualizer is overwritten when a connection is
established between the device and the ModbusTCP PLC.
Requirements:
ü IoT Core Visualizer has been started.
u Select the [Parameter] menu.
w The menu page shows the available parameters of the device.
9.2.3.1 Configuring a ModbusTCP interface
Changes to the byteswap data point will only take effect after the device has been restarted.
Available parameters:
Name Description Value range Access
[network] > [dhcp] Status of the DHCP client Static IP: Static IP address
DHCP: DHCP (Dynamic Host
Configuration protocol)
BOOTP: BOOTP (Bootstrap
Protocol)
rw
1
[network] > [ipaddress] IP address of the Ethernet interface e.g. 192.200.0.100
192.168.1.250 (default)
rw
1
[network] > [subnetmask] Subnet mask of the network segment e.g. 255.255.192.0
255.255.255.0 (default)
rw
1
[network] > [ipdefaultgateway] IP address of the network gateway e.g. 192.200.63.1
0.0.0.0 (default)
rw
1
[network] > [macaddress] MAC address of the Ethernet interface e.g. 00:02:01:0E:10:7C ro
2
[configuration] > [connection-
timeout]
Set timeout for interruption of the fieldbus
connection (value in milliseconds)
20: 20 ms
31000: 31000 ms
60000: 60000 ms
rw
1

Bekijk gratis de handleiding van IFM AL4043, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkIFM
ModelAL4043
CategorieNiet gecategoriseerd
TaalNederlands
Grootte5049 MB