IO-Link master with EtherNet/IP interface AL1921
47
9.2.11 Ports: Setting the operating mode Pin 4 (US)
Pin 4 of ports X01...X08 supports the following operating modes:
Disabled: No data transmission at pin 4 (C/Q) of the port
Digital input: Binary input signal at pin 4 (C/Q) of the port
Digital output Binary output signal at pin 4 (C/Q) of the port
IO-Link: IO-Link data transmission via pin 4 (C/Q) of the port
The set operating mode must match the operating mode of the device connected to the port (sensor,
actuator, IO-Link device).
Substructure: iolinkmaster/port[x] (x: 1…8)
Available data points:
Name Description Value range Access
…/mode Operating mode of pin 4 (US) of the
port
0: Disabled - port deactivated
1: DI - digital input
2: DO - digital output
3: IO-Link - IO-Link data
rw
1
2
../mastercycletime_actual Current cycle time of the data trans-
fer between port and IO-Link device
(value in µs)
0: best possible cycle time
1: 1 µs
132800: 132800 µs
ro
3
../comspeed Current transfer rate between port
and IO-Link device
0: COM1 - 4.8 kBaud
1: COM2 - 38.4 kBaud
2: COM3 - 230.4 kBaud
ro
3
../mastercycletime_preset Cycle time of the data transfer be-
tween port and IO-Link device (val-
ue in µs); only in IO-Link operating
mode
0: Automatically set the best possible cycle
time
1: 1 µs
132800: 132800µs
rw
1
2
1
Read and write
2
Read and write; parameter can only be changed if no active connection to fieldbus controller
3
Read only
9.2.12 Ports: Configuring device validation and data storage
The device supports the functions device validation and backup / restore of parameter data of the
connected IO-Link devices.
The following options are available:
Option
Validation of the connected
IO-Link device
Backup of parameter values
Restore of parameter val-
ues
[No check and clear] No No No
[Type compatible V1.0 de-
vice]
Yes, test compatibility with IO-
Link standard V1.0
No No
[Type compatible V1.1 de-
vice]
Yes, test compatibility with IO-
Link standard V1.1
No No
[Type compatible V1.1 de-
vice with Backup + Restore]
Yes, test compatibility with IO-
Link standard V1.1 and identity
of design (vendor ID, device
ID)
Yes, automatic backup of pa-
rameter values; Changes to
the current parameter values
will be stored
Yes, restore of parameter val-
ues when connecting an iden-
tical IO-Link device with facto-
ry settings
[Type compatible V1.1 de-
vice with Restore]
Yes, test compatibility with IO-
Link standard V1.1 and identity
of design (vendor ID, device
ID)
No, there is no automatic
backup; Changes to the pa-
rameter values are not stored
Yes, restore of parameter val-
ues when connecting an iden-
tical IO-Link device with facto-
ry settings