IFM AL1921 handleiding

135 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 48 van 135
AL1921 IO-Link master with EtherNet/IP interface
48
Device validation and backup / restore of parameter values are only available if the “IO-Link”
operating mode of the port has been activated.
For options [Type compatible V1.1 device with Backup + Restore] and [Type compatible V1.1
device with Restore]: If the parameters [Vendor ID] or [Device ID] are changed in online mode,
the data memory is deleted and the parameter values of the connected IO-Link device are
backed-up again in the IO-Link master.
Substructure: iolinkmaster/port[x] (x: 1…8)
Available data points:
Name Description Value range Access
../validation_datastor-
age_mode
Behaviour of the port when connecting a
new IO-Link device
0: No check and clear
1: Type compatible V1.0 device
2: Type compatible V1.1 device
3: Type compatible V1.1 device
with Backup + Restore
4: Type compatible V1.1 device
with Restore
rw
1
2
../validation_vendorid IO-Link ID of the manufacturer that is to be
validated
0…655535 rw
1
2
../validation_deviceid IO-Link ID of the device to be validated 0…16777215 rw
1
2
../datastorage Structure for port data storage - rw
1
2
../datastorage/maxsize Maximum size of the data storage content
(in bytes)
e.g. 2066: 2066 bytes ro
3
../datastorage/chunksize Size of a data segment (in bytes) e.g. 256: 256 bytes ro
3
../datastorage/size Size of the data storage content (in bytes) e.g. 1024: 2 bytes ro
3
1
Read and write
2
Read and write; parameter can only be changed if no active connection to fieldbus controller
3
Read only
Applicable services:
Name Description
../validation_useconnecteddevice Validate the IO-Link device
../datastorage/getblobdata Reading the content of the data storage area
../datastorage/stream_set Transfer an individual data segment
../datastorage/start_stream_set Start sequential transmission of several data segments
9.2.12.1 Example: Cloning the data memory of an IO-Link port
Task: The data memory of port 2 of IO-Link master 1 is to be cloned to IO-Link master 2.
Solution: The cloning consists of 2 steps. In the first step, the data memory of the port is read by IO-
Link master 1. In the second step, the read data is stored in the data memory of the port of IO-Link
master 2.
Read data memory
u Read segment size of the data storage (h = number of bytes)
{
"code":"request",
"cid": -1,
"adr":"/iolinkmaster/port[2]/datastorage/chunksize/getdata"
}
Example: h = 256