SolutionBlock IO-Link master AL1591
37
Name Description Value range Access
[Validation / Data Storage] Validation of the connected IO-Link
devices and automatic backup/re-
covery of the parameter sets of the
IO-Link device
No check and clear:
no validation
No data storage and data recovery
Type compatible V1.0 device:
Validation (IO-Link V1.0)
No data storage and data recovery
Type compatible V1.1 device:
Validation (IO-Link V1.1)
No data storage and data recovery
Type compatible V1.1 device with Backup
+ Restore:
Validation (IO-Link V1.1)
Data storage and data recovery
Type compatible V1.1 device with
Restore:
Validation (IO-Link V1.1)
Data recovery
No data storage
rw
1
2
[Vendor ID] Vendor ID of the IO-Link device to
be validated against
E.g. 310: ifm electronic gmbh rw
1
2
[Device ID] Device ID of the IO-Link device to
be validated against
E.g. 1129 TCC501 (ifm temperature sensor) rw
1
2
1
Read and write
2
Parameter only available if operating mode pin 4 (US) = IO-Link and IO-Link device is connected to the port
To configure the device validation and the backup / restore of parameter values:
Requirements:
ü ifm moneo|configure has been started.
ü The connection to the device is established (online).
ü Operating mode of pin 4 (US) of the port is IO-Link.
u Select the [Port x] > [IO-Link] menu (x = 1…8).
w The menu page shows the current settings.
u Set the parameters for device validation and backup / restore of parameter values.
u With active validation: Enter the manufacturer ID and device ID of the IO-Link device.
u Save the changes on the device.
w Device validation and backup / restore of parameter values have been configured.
9.1.5.4 Setting the cycle time
In the IO-Link operating mode, the cycle time of the port can also be set.
Available parameters:
Name Description Value range Access
[Cycle time actual] Current cycle time between the IO-Link
master and the IO-Link device (value in
µs)
1: 1 µs
132800: 132800µs
ro
1
[Cycle time preset] Cycle time between the IO-Link master
and the IO-Link device (value in µs)
NOTE!Observe the technical data of
the IO-Link device!
0: Fastest possible cycle time
1: 1 µs
132800: 132800µs
rw
2