If the access rights in the parameter setting software have been set to the [Fieldbus + IoT (read
only)] value, the access rights in the parameter setting software can no longer be changed. To
regain write access with the parameter setting software, set the access rights in the fieldbus
projection software to the [Fieldbus + IoT] value.
To configure the access rights:
Requirements:
ü The parameter setting software has been started.
ü The connection to the device has been established.
u Select the [IoT] menu.
w The menu page shows the current settings.
u Set the access rights.
u Write the changed values to the device.
u Restart the device.
w The changed access rights are active.
9.1.4 IoT: Configuring the interface to the monitoring software
To enable transmission of the process data of the IO-Link master to the monitoring software (e.g. ifm
moneo suite), the interface must be configured accordingly.
Available parameters:
Name Description Value range Access
IP address LR Agent or
SMARTOBSERVER
IP address of the monitoring soft-
ware
e.g. 255.255.255.255 (default) rw
1
Port LR Agent or SMARTOB-
SERVER
Port number of the monitoring soft-
ware
0: 0
35100: 35100 (default)
65535: 65535
rw
1
Interval LR Agent or SMAR-
TOBSERVER
Interval for data transmission to the
monitoring software (value in milli-
seconds)
Disabled: No transmission (default)
500: 500ms
2147483647: 2147483647ms
rw
1
Application tag Source identifier of the device in the
monitoring software
e.g., “factory 2 plant 1” rw
1
1
Read and write
To set the interface to the monitoring software:
After changing the parameters [Port LR Agent or SMARTOBSERVER] or [Application Tag], it
may take 120 seconds before the device establishes a new TCP connection.
To prevent the delay:
u When the parameter has been changed, restart the IO-Link master.
Requirements:
ü The parameter setting software has been started.
ü The connection to the device has been established.
ü The detailed view of the device is active.
u Select the [IoT] menu.
w The menu page shows the current settings.
u Set the parameters of the interface.