INSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS
Required Tools for Installation
5/8” (16mm), 7/8” (22mm), 1” (25mm) or adjustable
wrench
Adhesive tape
Conduit cable clamp ½”*
Copper line set
(refer to indoor specification for line
set size)
#2 phillips screwdriver
Drill
R32 flaring tool
Hex wrench
Hole saw 2 ï»๞
• Refrigerant scale
Level
Manifold gauge set
Measuring tape
Micron gauge
Mini-split adapter (຿»๛๠” F to ï»๞” M)
Nitrogen*
Pipe cutter
Razor knife
Reamer
Saddle clamp (L.S.) w/ screws
Sealant, non-expanding (for lineset hole)
Soap/water solution* or gas leakage detector
Stud finder
Torque wrench
Vacuum pump
Wire strippers
All usual and customary HVAC hand and power tools,
meters, and testing devices
* consumable
Supplied by Installer
Copper Refrigerant Line Set
Model Number Liquid (in) Vapor (in)
1H09HN2DA*
1/4
3/81H12HN2CA*
1H12HN2DA*
1H18HN2CA*
1/2
1H18HN2DA*
1H24HN2CA*
1H24HN2DA*
• 14/4 AWG SOOW copper stranded cable
• R32 refrigerant
• Refrigerant line insulation
• PVC drain pipe (optional)
Installation Precautions
R32 Air Conditioner Adding Extra Charge With Longer Pipe Calculator
Diameter of the liquid
connecting pipe (in)
Extra charge amount per foot
after standard length (oz)
1/4 0.2
Notes: Do not exceed maximum refrigerant amount listed in the
following table.
Important Information Regarding the Refrigerant Used
The standard pipe length without extra gas needed is 25ft;
the minimum pipe length is 10ft.
This product contains fluorinated greenhouse gases
covered by the Kyoto Protocol. Do not vent into the
atmosphere. Refrigerant type: R32