6.7 Inverter demand response modes (DRMS)
This series inverter has the function of demand response modes, We use 16-Pin socket as
inverter DRMS connection.
6.7.1 16-Pin socket pin assignment
No.
Description
Remarks
11
DRM1/5
Relay contact 1 input
12
DRM2/6
Relay contact 2 input
13
DRM3/7
Relay contact 3 input
14
DRM4/8
Relay contact 4 input
15
REF/GEN
GND
16
DRM0/COM
/
DRMS application description
Ø Applicable to AS/NZS4777.2:2015 or Commission Regulation
(EU) 2016/631.
Ø DRM0, DRM5, DRM6, DRM7, DRM8 are available.
Damage to the inverter due to moisture and dust penetration
Ø Make sure the cable gland has been tightened firmly.
Ø If the cable gland are not mounted properly, the inverter can be
destroyed due to moisture and dust penetration. All the warranty
claim will be invalid.
Information
CAUTION
WARNING
Excessive voltage can damage the inverter!
External voltage of DRM PORT don't over +5V.
6.7.2 Method of asserting demand response modes
Mode
Socket asserted by
shorting pins
Function
DRM 0
16
15
Operate the disconnection device.
DRM 5
11
15
Do not generate power.
DRM 6
12
15
Do not generate at more than 50% of rated power.
DRM 7
13
15
Do not generate at more than 75% of rated power and
reduce the reactive power as far as possible.
DRM 8
14
15
Increase power generation (subject to constraints from
other active DRMs).
6.7.3 Using the Power Control Interface for EU
Fig 6.13 Inverter – RRCR Connection
6.7.3.1 The following table describes the connector pin assignment and function:
DRM Socket Pin NO. Description
Connect to RRCR
11
12
13
14
15
Relay contact 2 input
Relay contact 3 input
Relay contact 4 input
GND
Relay contact 1 input
K2 – Relay 2 output
K3 – Relay 3 output
K4 – Relay 4 output
Relays common node
K1 – Relay 1 output
6.7.3.2The inverter is preconfigured to the following RRCR power levels:
DRM Socket
Pin 11
DRM Socket
Pin 12
DRM Socket
Pin 13
DRM Socket
Pin 14
Active power
Cos(φ)
Short circuit
with Pin 15
0%
1
Short circuit
with Pin 15
30%
1
Short circuit
with Pin 15
60%
1
Short circuit
with Pin 15
100%
1
Active power control and reactive power control are enabled separately.
24
23