Datasheet
Item
Parameter
General Data
Dimension(L/W/H)
90*45*65mm (Without buckle)
Weight
174g
Manual Language
Chinese,English
Environment Protection Rating
IP20
Mounting Type
Standard 35mm Rail
Certification
CEUKCARCMRoHS
Altitude
4000m
Electrical
Parameters
Application Scenario
Single Phase/Split
Phase/3P3W/3P4W
Single Phase
Rated Voltage
230Vac
1
Phase Voltage Range
100Vac - 416Vac
3P4W
Rated Voltage
230Vac/400Vac
1
Phase Voltage Range
100Vac – 416Vac
3P3W
Rated Voltage
230Vac/400Vac
Phase Voltage Range
100Vac – 240Vac
1
Line Voltage Range
173Vac – 416Vac
Split Phase
Rated Voltage
120Vac/240Vac
Phase Voltage Range
100Vac - 150Vac
Meter Rating
Class1
Starting Current
0.2% Ib
Ib
10A
CT
250A/40mA ,100A/40mA
Measurement Frequency
45-65Hz
Measurement Power
Active Power/Reactive
Power/Apparent Power
Average Power Consumption
1W
Operating Temperature Range
-30 65
Storage Temperature Range
-40 70
Operating Humidity
<85%RH
Pulse Constant
300imp/kWh
Datasheet
Item
Parameter
Application
Parameters
Communication Method
(Communication Distance)
RS485(200m)
Communication Protocol
MODBUS-RTU
Address Range
10-19
Bound Rate
9600bps,19200bps(Default),
38400bps
Update rate
100ms
Display
LED
Billing Function
None
Measurement
Accuracy
Voltage
0.5%
Current
0.5%
Frequency
0.2%
PF
1%
Active Power
1%
Reactive Power
2%
Apparent Power
1%
Active Energy
Class1
Reactive Energy
Class2
Fig 6.12
Active power control with a Radio Ripple Control Receiver(RRCR).