12.2.1 Inverter fault
Error code
Description
Troubleshooting
Error 200
DC arc fault has
been detected
1. After shutdown, check the connection of the
PV string.
2. Restart the inverter.
3. If the error message persists, please contact
Growatt support.
Error 201
An excessively
high leakage
current has been
detected
1. Restart the inverter.
2. If the error message persists, please contact
Growatt support.
Error 202
PV input voltage
exceeds the
upper threshold
1. Disconnect the DC switch immediately and
check the voltage.
2. If the PV input voltage is within the
permissible range and the error message
persists, please contact Growatt support.
Error 203
V panels have
low insulation
resistance
1. Check if the PV strings are properly grounded.
2. If the error message persists, please contact
Growatt support.
Error 204
PV string
reversely
connected
1. After shutdown, check if the PV string is
reversely connected to the inverter.
2. Restart the inverter.
3. If the error message persists, please contact
Growatt support.
Error 300
Grid voltage is
beyond the
permissible
range
1. Check the grid voltage.
2. If the grid voltage is within the permissible
range and the error message persists, please
contact Growatt support.
Error 301
AC terminals
reversed
1. Check the connection of the AC output
terminals.
2.If the error message persists, please contact
Growatt support.
Error 302
No utility grid
connected or
utility grid power
failure
1. After shutdown, check the AC wiring.
2. If the error message persists, please contact
Growatt support.
Error 304
Grid frequency is
beyond the
permissible
range
2. If the error message persists, please contact
Growatt support.
1. Check the grid frequency and restart the
inverter.
12.2 System fault
9089
Error code
Description
Troubleshooting
Error 305
Overload
1. Check if the load exceeds the output power
upper limit; if so, please reduce the load.
2. If the error message persists, please contact
Growatt support.
Error 309
ROCOF Fault
1. Check the grid frequency and restart the
inverter.
2. If the error message persists, please contact
Growatt support.
Error 311
Export limitation
fail-safe
1. After shutdown, check the connection of the
CT and the meter.
2. If the error message persists, please contact
Growatt support.
Error 401
High DC
component in
output voltage
1. Restart the inverter.
2. If the error message persists, contact Growatt
support.
Error 402
High DC
component in
output current
1. Restart the inverter.
2. If the error message persists, contact Growatt
support.
Error 403
Output current
unbalanced
1. Check if the output current is balanced after
shutdown.
2. If the error message persists, contact Growatt
support.
Error 404
Bus voltage
sampling
abnormal
1. Restart the inverter.
2. If the error message persists, please contact
Growatt support.
Error 405
Relay fault
1. Restart the inverter.
2. If the error message persists, please contact
Growatt support.
Error 407
Auto-test failed
1. Restart the inverter.
2. If the error message persists, please contact
Growatt support.
Error 408
Over-
temperature
1. After shutdown, check the temperature of the
inverter and restart the inverter after the
temperature is within the acceptable range.
2. If the error message persists, please contact
Growatt support.
Error 409
Bus voltage
abnormal
1. Restart the inverter.
2. If the error message persists, please contact
Growatt support.