Fault Simulation
6.2 Mode 2 (3-phase) Charging Cable
➭ Switch mains voltage on by turning the top rotary selector switch (S1) to the
Status C position (system state: vehicle ready for charging).
6.2.1 Simulated Interruption
➭ Start with the bottom rotary selector switch (S2) in the first ON position in the green area
for single-phase interruption.
➭ Switch through the positions, one after the other, in the clockwise direction (table from
top to bottom). Conductor interruption using a 3-phase, mode 3 charging cable as an
example:
Note
Tripping performance may deviate from this example in the case of ICCBs from other man-
ufacturers – adhere to the manufacturer’s test instructions!
6.2.2 Simulation of PE to Phase (PE-U
EXT
)
➭ Set the bottom rotary selector switch (S2) to the PE-U
EXT
position.
➭ Step 18: see section “Protective Conductor Current Measurement (IPE) at Mode 2
Charging Cable” on page 15
Step
Rotary
switch
Test Adapter
ICCB
Action
L1
LED
LED
L2
LED
L3
N
LED
PE
LED
LED
1
The test object’s correct reaction to the simulated fault can
be found in the manufacturer’s operating instructions.
2
3
4
5
6
7
8
Regarding step 8: The N LED also lights up due to star con-
nection, although N is interrupted!
9
10
Step
Rotary switch
Test Adapter
ICCB-IN1
Action
L1
LED
LED
L2
LED
L3
N
LED
PE
LED
LED
11
The test object’s correct reaction to the simu-
lated fault can be found in the manufacturer’s
operating instructions.