09 Maintenance
64
No. Fault Cause Solutions
5
Grid 10min
Overvoltage
The average
value of the
grid voltage
within 10
minutes
exceeds the
range speci󽗉ed
by safety
regulations.
1. If occurs occasionally, it may
be caused a short term grid
abnormality. The inverter will
recover automatically after the
grid is normal.
2. Check whether the grid voltage
has been operating at a relatively
high level for a long time. If the
problem occurs frequently, check
whether the grid voltage is within
the permissible range.
If the grid voltage exceeds
the allowable range, please
contact local power operator.
If the grid voltage is within the
allowable range, please modify
the Grid 10min Overvoltage
protection value with the
consent of the local power
operator.