09 Maintenance
63
No. Fault Cause Solutions
4
Grid
Undervoltage
The grid voltage
is below the
allowed range,
or the duration
exceeds the set
value of LVRT
duration.
1. If occurs occasionally, it may
be caused a short term grid
abnormality. The inverter will
recover automatically after the grid
is normal.
2. If it occurs frequently, please check
whether the grid voltage is within
the allowed range.
If the grid voltage exceeds the
allowable range, please contact
local power operator.
If the grid voltage is within the
allowable range, please modify
the Grid, HVRT or Overvoltage
protection value with the consent
of the local power operator.
3. If it does not restore for a long time,
please check whether the AC side
circuit breaker or output cables are
connected properly.