Goodwe EzLogger3000C handleiding
Handleiding
Je bekijkt pagina 59 van 135

08 System Commissioning
54
User Manual V1.2-2025-04-15
Protection Parameter Setting
Parameter Description
Overvoltage Trigger
n-order Value (0.1%)
Set the Level n overvoltage protection threshold, n=1, 2, 3, 4.
Overvoltage Trigger
n-order Trip Time
Set the Level n overvoltage protection duration, n=1, 2, 3, 4.
Undervoltage Trigger
n-order Value (0.1%)
Set the Level n undervoltage protection threshold, n=1, 2, 3, 4.
Undervoltage Trigger
n-order Trip Time
Set the Level n undervoltage protection duration, n=1, 2, 3, 4.
10min Overvoltage
Trigger Value (0.1%)
Set the 10-min overvoltage protection threshold.
10min Overvoltage Trip
Time
Set the 10-min overvoltage protection duration.
Overfrequency Trigger
n-order Value
Set the Level n overfrequency protection threshold, n=1, 2, 3, 4.
Overfrequency Trigger
n-order Trip Time
Set the Level n overvfrequency protection duration, n=1, 2, 3, 4.
Underfrequency
Trigger n-order Value
Set the Level n underfrequency protection threshold, n=1, 2, 3, 4.
Underfrequency
Trigger n-order Trip
Time
Set the Level n underfrequency protection duration, n=1, 2, 3, 4.
Start-up Grid
Connection Voltage
Upper Limit
The inverter cannot connect to the grid if it is powered on for the
rst connection and the grid voltage is higher than the Start-up Grid
Connection Voltage Upper Limit.
Start-up Grid
Connection Voltage
Lower Limit
The inverter cannot connect to the grid if it is powered on for the
rst connection and the grid voltage is lower than the Start-up Grid
Connection Voltage Lower Limit.
Parameter Description
Reactive Power Com-
pensation (Q/S)
Set the reactive power output from the inverter.
Reactive Power Com-
pensation Fixed Value
Adjust the reactive power output of the inverter by xed value.
Night Reactive Power
Function Switch
Enable or disable night reactive power function. In some specic application sce-
narios, the power grid company requires that the inverter can perform reactive
power compensation at night to ensure that the power factor of the local power
grid meets requirements.
Night Reactive Power
Parameters Taking Eect
Enable this function, the inverter outputs reactive power based on Fixed Value
of Night Reactive Power Scheduling. Otherwise, the inverter executes the
remote scheduling command.
Percentage of Night Re-
active Power Scheduling
(0.1%)
Schedule the reactive power by percentage during night reactive scheduling
period.
Fixed Value of Night Reac-
tive Power Scheduling
Schedule the reactive power by xed value during night reactive scheduling
period.